제품소개

Ring Main Unit
Ring Main Unit

Ring Main Unit

SF6 Ring Main Switch(SSPGS)

  • SF6 insulation and interruption LBS
  • Earthing switch
  • CT, voltage sensor and motorized
  • Certified in accordance with IEC 60265-1 and ANSI/IEEE 37.71 (1984)
Description SPG-15-6 SPGAS-2
Maximum System Voltage     15 Kv 25.8 kV
Rated Continuous Current  600 A 600 A
Rated Fault Making Current (peak) 52 kAp  32.5 kAp
Electrical Operating Time (Close/Open) 700 ms each 700 ms each
Number of Mechanical Operations (main) 5,000 times 5,000 times
Number of Mechanical Operations (ground) 1,000 times 1,000 times
Short Time Withstand Current (rms)  20 kA (4 sec) 12.5 kA (1sec)
Insulation Level Lightning Impulse Withstand Voltage         95 kV BIL 125 kV BIL
Power Frequency Withstand Voltage 50 kV  60kV
DC Voltage Withstand Voltage 53 kV 78 kV