Welcome to Shinsung
Your Source for
Power Distribution Protection &
Automation Equipment
Recloser
SF6 Gas Recloser
GENERAL FEATURES
- 3-phase SF6 gas insulated vacuum interruption auto circuit recloser for pole mounted or substation applications
- Integrated line sensors, vacuum interrupters, solenoid dual latch mechanism, dead line operation module and microprocessor based R6 relay to provide reliable operations without maintenance
- Certified in accordance with ANSI C37.60 (1981)
- RTU based μ-processor control
- Sef, Hif and open conductor fault protection
- Enhanced loop operation
TECHNICAL DATA
Description | SMRC-15 | SMRC-26 |
---|---|---|
Rated Maximum Voltage | 15.5 kV | 27 kV |
Rated Continuous Current | 630 A | 630 A |
Power Frequency Withstand Voltage (dry -1min / wet -10sec) | 50 kV / 45 kV | 60 kV / 50 kV |
Lightening Impulse Withstand Voltage (BIL) | 125 kV | 150 kV |
Rated Fault Making Capacity (peak) | 52 kAp | 32.5 kAp |
Rated Short Circuit Interrupting Current | 20 kA | 12.5 kA |
Mechanical/Electrical Operations | 10,000 times | 10,000 times |